Description
CHEMGUARD® NFF 3x3 UL201 is a 3%x3% Alcohol Resistant Non-Fluorinated Foam Concentrate that provides excellent fire and vapor suppression for Class B, polar solvent and hydrocarbon fuel fires. This synthetic foam concentrate is intended for forceful or gentle firefighting applications at 3% solution on hydrocarbon fuels and gentle firefighting applications at 3% solution on polar solvent fuels. CHEMGUARD NFF 3x3 UL201 foam solution utilizes three suppression mechanisms intended for rapid fire knockdown and superior burnback resistance:
CHEMGUARD NFF 3x3 UL201 is defined as a non-fluorinated firefighting foam concentrate, produced in equipment free from the use of PFAS chemistry. Since this product is free from any intentionally added PFAS chemistry, and precautions have been used to avoid PFAS contamination, the concentrate inherently complies with Directives (EU) 2017/1000 on PFOA and 2019/1021 (EU POPs directive) as a non-fluorinated product.
CHEMGUARD NFF 3x3 UL201 Foam Concentrate is a nonNewtonian fluid that is both pseudoplastic and thixotropic. Due to these properties, dynamic viscosity will decrease as shear increases. Features
ApplicationCHEMGUARD NFF 3x3 UL201 Foam Concentrate is intended for use on both types of Class B fires: hydrocarbon fuels with low water solubility, such as crude oils, gasolines, diesel fuels, and aviation fuels; and polar solvent fuels with appreciable water solubility, such as methyl and ethyl alcohol, acetone, and methyl ethyl ketone. The concentrate has excellent wetting properties that can effectively combat Class A fires. It may also be used in conjunction with dry chemical agents to provide even greater fire suppression performance. CHEMGUARD NFF 3x3 UL201 is well-suited for use in applications such as municipal and industrial response for spill and limited scale Type III hazards as well as foam systems with Type II discharge devices. Examples of these applications include:
Application Rates
(1) TYPE III DISCHARGE OUTLET – A device that delivers the foam directly onto the burning liquid as described in UL-162. (2) NFPA 11 allows a design rate of 0.10 gpm/ft2 (4.1 Lpm/m2) for spill fire applications. This product has been tested in accordance with UL 162 for use at this application rate. (3) TYPE II DISCHARGE OUTLET – A device that delivers foam onto the burning liquid and partially submerges the foam or procedures restricted agitation of the surface as described in UL-162. Foaming PropertiesCHEMGUARD NFF 3x3 UL201 Foam Concentrate may be effectively applied using most conventional foam discharge equipment at the correct dilution with fresh, salt, or hard water.
ProportioningThe recommended operational temperature range for CHEMGUARD NFF 3x3 UL201 Foam Concentrate is 35 °F to 120 °F (2 °C to 49 °C) per UL162. This foam concentrate can be correctly proportioned using most conventional, properly calibrated, in-line proportioning equipment such as:
Storage and HandlingCHEMGUARD NFF 3x3 UL201 Foam Concentrate should be stored in the original supplied package (HDPE totes, drums, or pails) or in the recommended foam system equipment as outlined in Johnson Controls Technical Bulletin Storage of Foam Concentrates. The concentrate should be maintained within the recommended operational temperature range. Freezing of the product should be avoided. Factors affecting the foam concentrate’s long-term effectiveness include temperature exposure and cycling, storage container characteristics, air exposure, evaporation, dilution, and contamination. The effective life of CHEMGUARD NFF 3x3 UL201 can be maximized through optimal storage conditions and proper handling. CHEMGUARD foam concentrates have demonstrated effective firefighting performance with contents stored in the original package under proper conditions for more than 10 years. This product should not be mixed with other types of foam concentrates or other manufacturer's foam concentrates under any circumstances. The use of multiple, separately applied finished foam products for incident response is appropriate. InspectionCHEMGUARD NFF 3x3 UL201 Foam Concentrate should be inspected periodically in accordance with NFPA 11, EN 13565-2, or other relevant standard. A representative concentrate sample should be sent to Johnson Controls Foam Analytical Services or other qualified laboratory for quality analysis per the applicable standard. An annual inspection and sample analysis is typically sufficient, unless the product has been exposed to unusual conditions. Ordering Information
Safety Data Sheets (SDS) are available at www.chemguard.com If any foam product is discharged into the environment, efforts should be made to control, contain and collect the discharge for proper disposal, while following all applicable laws, regulations, and codes. Further information regarding the use, discharge, and disposal of firefighting foams can be found at www.chemguard.com. Note: The converted metric values in this document are provided for dimensional reference only and do not reflect an actual measurement. CHEMGUARD® and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. |